-40%

Omron S8VS-12024B 24 VDC power supply with current voltage display 120W 5A

$ 66

Availability: 14 in stock

Description

DC power supply made by Omron.  This is a new item in its original box.
PN:
S8VS-12024B
Covered type, Natural air-cooling, Input: 80 to 370 VDC 100 to 240 VAC, Power ratings: 120 W, Output: 24 VDC
Power rating
120 W
Rated input voltage
100 to 240 VAC
Output voltage
24 VDC
Heat radiation
Natural air-cooling
Construction
Covered type
Terminal type
Screw terminal
Mounting type
DIN Rail mounting type
As of November 11, 2015
Power rating
120 W
Efficiency
83% TYP.(At 100 VAC input)
85% TYP.(At 200 VAC input)
Rated input voltage
100 to 240 VAC
Allowable input voltage variable range
85 to 264 VAC
80 to 370 VDC
Note at DC input
The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 VAC (85 to 264 VAC).
Frequency
50/60 Hz(47 to 63 Hz Single-phase)
Rated input curren
1.5A TYP. (At 100 VAC input)
0.72A TYP. (At 200 VAC input)
Power factor
0.9 Min.
Leakage current
0.5 mA Max. (At 100 VAC input)
1.0 mA Max. (At 200 VAC input)
Inrush current
14 A TYP. (At 100 VAC input (For cold start at 25 CEL))
28 A TYP. (At 200 VAC input (For cold start at 25 CEL))
Output voltage
24 VDC
Output voltage variable range
-10 to +15 % (With V. ADJ)
(The output voltage may increase beyond the allowable voltage range (up to +15% of the rated voltage) depending on the operation of the output voltage adjuster (V.ADJ). When adjusting the output voltage, check the output voltage of the Power Supply and be sure that the load is not damaged.)
Ripple
2%(p-p) Max. (Under the rated I/O conditions.)
130mV Max. (Under the rated I/O conditions.)
Static input variation influence
0.5% Max. At 85 to 264 VAC input, 100% load
Static load variation influence
1.5% Max. At rated input, 0 to 100% load
Ambient temperature variation influence
0.05 %/CEL Max.
Rated output current
5 A
Start up time
650 ms TYP. (100 VAC input)
520 ms TYP. (200 VAC input)
Hold time
56ms TYP. (100 VAC input)
56ms TYP. (200 VAC input)
Overload protection
105% to 160% of the rated output current
Inverted L voltage drop, Automatic reset
Overvoltage protection
Operated at 130% Min. of the rated output voltage, Shut-off
Resetting: Reset the power by turning it back (OFF time: at least 3 min)
Overheat protection
No
Output voltage indication
Yes (Resolution: 0.1V / Accuracy: +/- 2% (percentage of output voltage value) +/- 1 digit Max.)
Output current indication
Yes (Resolution: 0.1A / Accuracy: +/- 5% F.S. (percentage of rated output current value) +/- 1 digit Max.)
Peak-hold current indication
Yes (Resolution: 0.1A / Accuracy: +/- 5% F.S. (percentage of rated output current value) +/- 1 digit Max. / Minimum_detectable_signal_width: 10 ms (20 ms Max.))
Maintenance forecast monitor output
No
Total run time monitor indication
Yes (Resolution: 1 kh / Setting range: 1 to 150 kh)
Total run time monitor output
Yes (open collector output), 30 VDC Max., 50 mA Max., Sinking (NPN)
Undervoltage alarm indication
Yes (Resolution: 0.1 V / Setting range: 18.5 to 27.5 V)
Undervoltage alarm output
Yes (open collector output), 30 VDC Max., 50 mA Max., Sinking (NPN)
Power failure alarm output
No
Parallel operation
No (However, backup operation is possible; external diodes required.)
N+1 redundant system
-
Series operation
Yes (Up to 2 Power Supplies with external diode)
Remote sensing function
No
Dielectric strength
Between all inputs and all outputs/alarm outputs: 3 kVAC for 1 min (Detection current: 20 mA)
Between all inputs and PE terminals: 2 kVAC for 1 min (Detection current: 20 mA)
Between all outputs/alarm outputs and all PE terminals: 1 kVAC for 1 min (Detection current: 20 mA)
Between all outputs and all alarm outputs: 500 VAC for 1 min (Detection current: 20 mA)
Insulation resistance
Between all outputs/alarm outputs and all inputs/PE terminals: 100 MOhm Min. (at 500 VDC)
Vibration resistance
10 to 55 Hz, 0.375 mm single amplitude in each 3 directions for 2 hours
Shock resistance
150 m/s**2, in each 6 directions 3 times
Output indicator
Yes (color: green)
Heat radiation
Natural air-cooling
Construction
Covered type
Terminal type
Screw terminal
Mounting type
DIN Rail mounting type
Weight (Main)
Approx. 550 g
Thanks for looking!  Please browse my store for more power supplies and other automation equipment.